Vicom
             


Fire Alarm System - Audible/Visible Notification

Spectralert Selectable Output Outdoor Horns and Strobes - P1224MCK/S1224MCK/H12/24

 
Description & Specifications
 
The Selectable Output Outdoor Horns and Strobes contain the same features as the indoor horns and strobes and are UL listed NEMA 3 approved.

Red Model No Candela FWR Operating Current-Strobe (mA RMS) DC Operating Current-Strobe (mA RMS) FWR Operating Current-Horn (mA RMS) DC Operating Current-Horn (mA RMS)

12V 24V 12V
24V 12V
24V 12V
24V
P1224MCK 15 112 64 127 59 46 58 44 57
  15/75 135
74 127 69 46 58 44 57
30 N/A 93 N/A 90 46 58 44 57
75 N/A 158 N/A 160 46 58 44 57
110 N/A 208 N/A 209 46 58 44 57
S1224MCK 15 112 64 127 59 -- -- -- --
  15/75 135
74 127 69 -- -- -- --
30 N/A 93 N/A 90 -- -- -- --
75 N/A 158 N/A 160 -- -- -- --
110 N/A 208 N/A 209 -- -- -- --
H12/24K N/A N/A N/A N/A N/A 46 58 44 57
*For outdoor application, mount devices to weatherproof back box, model WBB
Copyright © 2006-2007 Vicom India. All rights reserved. Powered by : Net Dunes